| Parameter Category | Parameter Name | Value |
|---|---|---|
| General Information | ||
| Product Type | MICROMASTER 440 Universal Inverter Drive | |
| Order Number | 6SE6440-2UD21-5AA1 | |
| Product Status | Discontinued (Still available as spare part) | |
| Main Application | Constant torque and variable torque loads (e.g., conveyors, mixers, pumps, fans) | |
| Control Modes | Vector control, V/f control, Sensorless vector control | |
| Input Specifications | ||
| Input Voltage | 380-480 V 3-phase AC | |
| Input Frequency | 47-63 Hz | |
| Voltage Tolerance | +10% / -10% | |
| Connection Type | 3-phase with protective conductor | |
| Output Specifications | ||
| Rated Output Power (CT) | 1.5 kW (2.0 hp) | |
| Rated Output Power (VT) | 1.5 kW (2.0 hp) | |
| Rated Output Current | 4.1 A | |
| Output Voltage | 0...0.97 × Uline (3-phase AC) | |
| Output Frequency Range | 0...650 Hz | |
| Switching Frequency | 2...16 kHz (adjustable) | |
| Overload Capacity | ||
| Overload 1 (60 s) | 150% of rated current (6.15 A) | |
| Overload 2 (3 s) | 200% of rated current (8.2 A) | |
| Overload 3 (0.5 s) | 250% of rated current (10.25 A) | |
| Dimensions | ||
| Width | 73 mm (2.87 in) | |
| Height | 173 mm (6.81 in) | |
| Depth | 149 mm (5.87 in) | |
| Weights | ||
| Net Weight | Approx. 1.3 kg (2.87 lb) | |
| Ambient Conditions | ||
| Operating Temperature | -10°C to +50°C (14°F to 122°F) | |
| Storage Temperature | -25°C to +70°C (-13°F to 158°F) | |
| Max Altitude | 1000 m (3281 ft) above sea level (derate above 1000 m) | |
| Relative Humidity | 5% to 95% (non-condensing at 25°C) | |
| Protection Class | IP20 (NEMA 1) | |
| Electrical Characteristics | ||
| Power Factor (cos φ) | >0.95 at rated load | |
| Efficiency | >96% at rated load | |
| Power Loss | Approx. 45 W | |
| Braking Resistor | Optional (external) | |
| DC Link Voltage (400V) | 540 V DC (typical) | |
| Communication Interface | ||
| Built-in Interfaces | RS485 (Modbus RTU, USS protocol) | |
| Optional Interfaces | PROFIBUS DP, DeviceNet, CANopen | |
| Safety Features | ||
| Integrated Safety Functions | Overcurrent protection, Overvoltage protection, Undervoltage protection, Overheating protection, Earth fault protection, Short circuit protection | |
| EMC Compliance | ||
| Standard Compliance | EN 61800-3, IEC 61800-3 | |
| Built-in Filter | No (optional external filter available) | |
| Cooling System | ||
| Cooling Type | Convection cooling (natural cooling) | |
| Ambient Temperature Derating | 100% load up to 40°C, derate 2.5% per °C above 40°C | |
| Additional Features | ||
| Braking Chopper | Optional (built-in for some models, external for this model) | |
| Control Panel | BOP-2 (Basic Operator Panel) optional, SDP (Smart Digital Panel) optional | |
| Analog Inputs | 2 x 0-10 V / 0-20 mA (configurable) | |
| Digital Inputs | 6 x digital inputs (configurable) | |
| Digital Outputs | 2 x relay outputs (configurable) | |
| Analog Outputs | 2 x 0-20 mA (configurable) | |