| Parameter | Value |
|---|---|
| Model Number | 6SL3210-1PE11-8UL1 |
| Product Description | SINAMICS Power Module PM240-2 unfiltered with integrated braking chopper |
| Series | SINAMICS G120 |
| Input Voltage | 380-480 V AC +10/-10% |
| Input Phase Number | 3 |
| Input Frequency | 47-63 Hz |
| Input Current (Low Overload - LO) | 2.3 A |
| Input Current (High Overload - HO) | 2 A |
| Output Voltage | 0-480 V AC (depending on input voltage) |
| Output Phase Number | 3 |
| Output Frequency | 0-600 Hz |
| Output Current (LO) | 2.6 A |
| Output Current (HO) | 1.7 A |
| Rated Power (LO) | 0.55 kW (0.75 HP) |
| Rated Power (HO) | 0.37 kW (0.5 HP) |
| Overload Capability (LO) | 150% for 3 s, 110% for 57 s, 100% for 240 s |
| Overload Capability (HO) | 200% for 3 s, 150% for 57 s, 100% for 240 s |
| Degree of Protection | IP20 / UL open type |
| Braking Chopper | Integrated |
| Filter Class | Unfiltered |
| Parameter | Value |
|---|---|
| Efficiency (η) | 0.96 |
| Power Factor (λ) | 0.85 |
| Offset Factor (cos φ) | 0.95 |
| Sound Pressure Level (1m) | 72 dB |
| Power Loss | 0.04 kW |
| Cooling Air Requirement | 5 l/s |
| Cooling Method | Forced air cooling (push-through technology) |
| Parameter | Value |
|---|---|
| Ambient Temperature (Operation LO) | -10 to +40 °C |
| Ambient Temperature (Operation HO) | -10 to +50 °C |
| Ambient Temperature (Storage/Transport) | -25 to +70 °C |
| Relative Humidity | 5-95% (non-condensing) |
| Installation Altitude | Up to 1000 m (derating above 1000 m) |