LC1D95 Core Parameters (TeSys D Series 95A Three-Pole Contactor)
Model Meaning: LC1 = Contactor; D = Three-Pole Standard; 95 = AC-3 Rated 95A
Main Circuit: 3NO; AC-3: 95A / 400V; AC-1: 145A; Rated Insulation Voltage 1000V
Applicable Motors: 55kW (400V) / 30kW (220V)
Auxiliary Contacts: Standard 1NO + 1NC
Coil Voltage: AC24/110/220/380V; DC24/48/110V
Common Models: LC1D95M7C (AC220V), LC1D95Q7C (AC380V), LC1D95BDC (DC24V)
Protection: IP20; Operating Temperature: -25℃~+60℃
Mounting: 35mm DIN Rail / Panel mount; Dimensions: 85×127×130mm; Weight ≈ 1.3kg
Lifespan: Mechanical life ≈ 30 million cycles; AC-3 electrical life ≈ 1.5–2 million cycles
Certifications: CCC, CE, UL, IEC 60947-4-1, RoHS
Applications: 55kW motors, fans, water pumps, air compressors, crushers, machine tools, switch cabinets, star-delta/reversible starters