LC1D50A Core Parameters (TeSys D Series 50A Three-Pole Contactor)
Model Meaning: LC1 = Contactor; D = Three-Pole Standard; 50A = AC-3 Rated 50A
Main Circuit: 3NO; AC-3: 50A/400V; AC-1: 75A; Rated Insulation Voltage: 690V
Applicable Motors: 22kW / 30kW (400V); Standard Common: 30kW
Auxiliary Contacts: Standard 1NO + 1NC
Coil Voltage: AC24/110/220/380V; DC24/48/110V
Common Models: LC1D50AM7C (AC220V), LC1D50AQ7C (AC380V), LC1D50ABDC (DC24V)
Protection: IP20; Operating Temperature: -25℃~+60℃
Mounting: 35mm DIN Rail / Screw mounting; Dimensions: 55×95×115mm; Weight ≈720g
Lifespan: Mechanical life ≈ 30 million cycles; AC-3 electrical life ≈ 1.5–2 million cycles
Certifications: CCC, CE, UL, IEC 60947-4-1, RoHS
Applications: 30kW motors, fans, water pumps, air compressors, injection molding machines, distribution cabinets, star-delta/reversible starters