Core Positioning and Functions
2-channel single-ended 0…10 V voltage input EtherCAT terminals, 16-bit resolution (including sign bit)
Supports distributed clocks for high-precision synchronous acquisition; FIR/IIR digital filtering and limit monitoring alarms can be enabled.
No additional configuration required, plug and play; independent LED status indicators for each channel; 500 V electrical isolation between E-bus and signal, resistant to industrial interference.
Standard/compact process images are available to adapt to different PLC memory resources; conversion time is approximately 50 μs, suitable for medium-to-high-speed signal acquisition.
Key Technical Parameters
Table Parameter Value Input Channels 2 single-ended, 0~10 V; internal resistance > 200 kΩ
Resolution 16 bit (including sign)
Measurement Error < ±0.3% FS
Conversion Time ~50 μs; input filter limit frequency 5 kHz
Electrical Isolation E-bus / Signal 500 V; common ground between channels
E-bus Current Consumption Typical 170 mA
Operating Temperature -25℃ ~ +60℃
Storage Temperature: -40℃ ~ +85℃
Protection Rating: IP20
Dimensions: 24 mm × 100 mm × 52 mm (DIN rail standard size)
Weight: Approx. 60 g
Certifications: CE, UL, CCC, ATEX, IECEx, etc.
Installation and Typical Applications: 35 mm DIN rail mounting (compliant with EN 60715), dual-slot side-by-side mounting
Typical Scenarios: Production line pressure/level/temperature transmitter (0-10V output) acquisition, building automation analog quantity monitoring, printing/packaging machinery tension/position feedback, photovoltaic/lithium battery equipment process parameter monitoring