| Parameter | Specification |
|---|---|
| Brand / Model | Schneider Electric LRD32C (TeSys D Series) |
| Product Type | 3-Pole Differential Thermal Overload Relay |
| Setting Current Range | 23–32A (Adjustable) |
| Trip Class | Class 10A (Fast tripping: ~7.2s at 1.5x current) |
| Auxiliary Contacts | 1NO + 1NC (95-96 NC, 97-98 NO) |
| Contact Capacity | 5A / 690V AC |
| Installation Method | Direct mount below LC1-D25–D38 contactors or DIN rail (TH35) |
| Reset Method | Manual (H) / Automatic (A) optional |
| Physical Dimensions | 45 * 66 * 70 mm (W * D * H) |
| Weight | Net: 0.18 kg / Gross: 0.22 kg |
| Protection Rating | IP20 (Indoor control cabinet use) |
| Operating Temperature | -20℃ to +60℃ |
| Storage Temperature | -40℃ to +85℃ |
| Certifications | CE, UL 61010, CSA, RoHS, Green Premium |
| Country of Origin | France |
| Component | Function |
|---|---|
| White Scale Knob | Setting current Ir (23–32A) |
| Toggle Window | Test button + Trip indicator (T) |
| Red Button | Stop (Forced disconnect 95-96) |
| Blue Button | Reset (Manual reset) |
| H/A Switch | Manual/automatic reset selection |
| Lead Seal Hook | Lock setting parameters |