Schneider LC1D32M7C TeSys Deca Contactor with 32A Rated Current 3P Poles DIN Rail Mounting

1
MOQ
Negotiable
Price
Schneider LC1D32M7C TeSys Deca Contactor with 32A Rated Current 3P Poles DIN Rail Mounting
Features Gallery Product Description Chat Now
Features
Specifications
Mounting_Type: DIN Rail
Power_Consumption: 5 W
Point: 14 (8DI+6DO)
Mpu Points: 12 (8DI + 4DO)
Weight: 0.3 Kg
CPU_Speed: 100 MHz
Input_Voltage: 24 V DC
Points: 40 (24DI+16DO)
Actual Price: Based On Offer
Memory: 50 KB
Number_of_Outputs: 10
Application: Oil And Gas Factory
Input Points: 100-2
Operating_Temperature_Range: -20°C To 60°C
Part Type: Sysmac CPM2A
Highlight:

32A Rated Current Contactor

,

3P Number of Poles TeSys Deca Contactor

,

DIN Rail Mounting Schneider Contactor

Basic Infomation
Brand Name: Schneider
Certification: Brand new original
Model Number: LC1D32M7C
Document: LC1D32M7C.pdf
Payment & Shipping Terms
Delivery Time: 5-7 days
Payment Terms: T/T
Supply Ability: 1000
Product Description
Schneider LC1D32M7C Contactor
Product Series:
TeSys Deca
Product Type:
Contactor
Short Product Name:
LC1D
Application Areas
  • Applicable to AC loads with a power factor greater than or equal to 0.95
  • Applicable to non-inductive or slightly inductive loads, resistance furnaces
Usage Categories
  • AC-4
  • AC-1
  • AC-3
  • AC-3e
Electrical Specifications
Parameter Specification
Number of Poles 3P
Rated Operating Voltage [Ue] Power Circuit: ≤ 690 V AC 25...400 Hz
Power Circuit: ≤ 225 V DC
Rated Operating Current [Ie] 32 A (≤ 60°C) when operating voltage ≤ 440 V AC (AC-3)
50 A (≤ 60°C) when operating voltage ≤ 440 V AC (AC-1)
32 A (≤ 60°C) when operating voltage ≤ 440 V AC (AC-3e)
Control Circuit Voltage [Uc] 220 V AC 50/60 Hz
Motor Power Ratings
Operating Voltage Power (kW) Usage Category
≤ 500 V AC 50/60 Hz 18.5 kW AC-3
≤ 220/240 V AC 50/60 Hz 7.5 kW AC-3
≤ 380/400 V AC 50/60 Hz 15 kW AC-3
≤ 415/440 V AC 50/60 Hz 15 kW AC-3
≤ 660/690 V AC 50/60 Hz 18.5 kW AC-3
≤ 400 V AC 50/60 Hz 7.5 kW AC-4
Technical Details
Circuit Contact Type:
3 NO
Protective Cover:
With
Rated Thermal Current [Ith]:
10 A (≤ 60°C) for signal circuits
50 A (≤ 60°C) for power circuits
Performance Characteristics
Parameter Value
Mechanical Life 15 Mcycles
Electrical Life (AC-3, 32A, ≤440V) 1.6 Mcycles
Electrical Life (AC-3, 22A, 660/690V) 2.6 Mcycles
Maximum Operating Frequency 3600 cycles/hour at 60°C
Action Time (Closing) 12-22 ms
Action Time (Breaking) 4-19 ms
Control Circuit Specifications
Power Consumption (Start):
70 VA at 50/60 Hz, cos φ 0.75 (at 20°C)
Power Consumption (Hold):
6-7 VA at 50/60 Hz, cos φ 0.3 (at 20°C)
Heat Dissipation:
1.5-2.5 W at 50/60 Hz
Recommended Products
Get in touch with us
Contact Person : Leon Lee
Tel : +8615389206502
Fax : 86--15389206502
Characters Remaining(20/3000)