| Item | Technical Specification |
|---|---|
| Brand | Pepperl+Fuchs |
| Model | KCD2-SOT-EX2 |
| Product Type | 2-channel Intrinsic Safety Switch Amplifier / Frequency Signal Conditioner |
| Hazardous Zone Rating | II(1)G [Ex ia Ga] IIC; II(1)D [Ex ia Da] IIIC |
| Functional Safety | SIL 2, SC3 (IEC/EN 61508) |
| Input Signal Type | NAMUR sensor / Dry contact digital frequency signal |
| Supply Voltage | 19 ~ 30 V DC (Rated 24VDC), Ripple ≤10% |
| Power Dissipation | ≤ 800 mW |
| Max Switching Frequency | 5 kHz (High-speed frequency pulse transmission) |
| Input Circuit Parameter | Open circuit voltage ~10VDC, Short-circuit current ~8mA |
| Switching Hysteresis | 1.2 ~ 2.1 mA, Hysteresis 0.2mA |
| Line Fault Detection | Open circuit ≤0.1mA; Short circuit ≥6.5mA |
| Output Type | 2-channel Passive Transistor Output, Max 30VDC / 50mA per channel |
| Response Time | ≤200μs, Stable frequency signal output |
| Signal Logic | Reversible NO/NC mode via DIP switch |
| Galvanic Isolation | Reinforced insulation 300V eff between field & control side |
| Mounting Method | Standard 35mm DIN rail (EN 60715) |
| Housing Dimension | 12.5mm(W) × 119mm(H) × 114mm(D) |
| Single Net Weight | Approx. 100g / pc |
| Connection Terminal | Spring clamp terminal, easy wiring without screwdriver |
| Protection Grade | IP20 (Indoor control cabinet use) |
| Ambient Working Temp | -20℃ ~ +60℃, Extended to 70℃ under limited installation |
| Certifications | ATEX, IECEx, UL, SIL2, RoHS, CE |